Clean Air Control
The Clean Air Control function is used in ventilation sys-
tems where the aim is to regulate the airflow according to
the content of emission/impurities in the room air.
One VOC sensor (Volatile Organic Compound) is mounted
as standard inside COMPACT Air & Heat units. For COM-
PACT Unit & Top units, the VOC sensor (TBLZ-1-60) is an
accessory and must be ordered separately.
The VOC sensor measures the content of emissions/impu-
rities in % VOC.
When an occupant emits CO
2
, this creates a proportional
amount of emissions/impurities which are measurable by
the VOC sensor. For an approximate translation of the %
VOC to CO
2
content, see the diagram.
When the VOC sensor measures contents of emissions/
impurities that are lower than the preset value; the air
handling unit’s supply air and extract air flows are then
equivalent to the preset min. flows. When the VOC sen-
sor instead measures contents of emissions/impurities that
are higher than the preset limit value, the supply air and
extract air flows are variably increased until the preset
value or max. flow is reached.
1000
1500
2000
400
10 20 30 40 50 60 70 80 90
% VOC
CO
2
content, ppm
Example:
800 ppm is equivalent to approx. 30% VOC.
If influenced by other emissions/impurities in the air, such
as cooking odours, cigarette smoke, etc., the VOC con-
tent increases in relation to the CO
2
content.